Can you tie grounds together from different circuits?

I usually tie them together but this time I thought it was cleaner to separate them. both circuits are properly grounded at the sub panel. The inspector said that for the past 30 years the code has required that all equipment grounds be tied together regardless of what circuit they originate from.
Takedown request   |   View complete answer on forums.mikeholt.com


Can grounds be shared between circuits?

The code requires each branch circuit to have an equipment ground (either a wire, or conduit, or cable tray as in 250.120A), they can be shared when they are in the same raceway. If all the 20A circuits are in one raceway then you just need one ground.
Takedown request   |   View complete answer on engineerboards.com


Can you connect multiple grounds together?

No you can't.
Takedown request   |   View complete answer on diy.stackexchange.com


Should all grounds be connected together?

Ground wires must be firmly connected at all points. And if conduit or sheathing is used as a ground path, connections must be tight. If you're not sure if your outlets are grounded, a receptacle analyzer will tell you.
Takedown request   |   View complete answer on bhg.com


Can you combine neutrals together from different circuits?

As these joined neutrals include the travelers of both three-way circuits, the neutrals from the nearest light to each box, and the neutral heading back to the panel from each box, these two circuits' neutrals have multiple junction points that tie the neutrals together.
Takedown request   |   View complete answer on diy.stackexchange.com


Why Neutrals



What happens when two neutrals touch?

If two neutrals are under one lug and you only switch off one circuit breaker the second circuits return path will remain energized causing a dangerous hazard if contact is made by the electrician or arcing if the neutral wire comes in contact with any grounded parts of the panel.
Takedown request   |   View complete answer on forum.nachi.org


Can 2 circuits share a breaker?

Yes, it's fine to combine circuits onto one breaker, at which point they become one circuit.
Takedown request   |   View complete answer on diy.stackexchange.com


Can ground wires from different circuits touch?

So if your area has adopted NEC 2014, you can connect a grounding conductor to the grounding conductor from another branch circuit, as long as both circuits originate from the same panel.
Takedown request   |   View complete answer on diy.stackexchange.com


Is it okay to connect 2 ground wires together?

The two ground wires must be wire-nutted together along with another 6-inch length of green or bare ground wire known as a pigtail. A grounded electrical outlet has three holes to provide a ground connection for three-prong plugged devices.
Takedown request   |   View complete answer on homesteady.com


Can 2 power supplies share a common ground?

If the two power supplies share a common ground, or can be made to, then it is no problem. However, the return wire must be sized for the sum of the 8 V and 12 V currents.
Takedown request   |   View complete answer on forum.allaboutcircuits.com


Can two circuits share a neutral and ground?

What is a multiwire branch circuit? A multiwire branch circuit is a branch circuit with a shared neutral. This means there are two or more ungrounded (hot) phase or system conductors with a voltage between them and a shared neutral.
Takedown request   |   View complete answer on electricalnews.com


Can 2 GFCI share the same ground?

Using two individual breakers does not work because of the way that GFCI breakers are designed. They ensure that current flowing into the load on the hot wire is equal to the current flowing out of the load in the neutral wire.
Takedown request   |   View complete answer on diy.stackexchange.com


How many grounds can go under one lug?

While panel manufacturers will allow for up to three grounding conductors under a single lug, they typically only allow one neutral wire.
Takedown request   |   View complete answer on structuretech.com


Can you ground 2 amps in the same spot?

As long as both amps are grounded to the same spot you should be able to avoid ground loop. Runing to a distro or running both grounds to the same spot ends up with the same result.
Takedown request   |   View complete answer on diymobileaudio.com


Can grounds touch?

A ground wire can touch itself without any risk. That's because one wire doesn't make a circuit, it takes two wires or more, or a physically-grounded component in conjunction with a wire to do that. In both AC and DC circuits, it works the same way.
Takedown request   |   View complete answer on homex.com


What is a piggyback circuit breaker?

A double circuit breaker takes the space of a single circuit breaker on a panelboard. Depending on local customs, they are called duplex, slimline, twin, half-height, half-inch, double and waferbreakers.
Takedown request   |   View complete answer on homex.com


Are tandem breakers legal?

Tandem breakers are safe and legal to use only when the panel is designed for them and only in the slots that accept tandem breakers.
Takedown request   |   View complete answer on thespruce.com


What is a double tapped circuit?

A double tapped breaker is basically two wires under one circuit breaker that is designed for one wire. You can see what this looks like in the picture above. The issue with double tapping is you could technically have a loose connection or an overloaded breaker since the breaker is not designed for two wires.
Takedown request   |   View complete answer on waypointinspection.com


Can neutral wires touch each other?

If you touch the neutral wire in a live circuit, whether it be a lamp, an appliance or something else, it is the same as touching the active wire. It is only "safe" to touch the neutral wire when there is no current flowing, just as it is "safe" to touch the earth wire (when one exists).
Takedown request   |   View complete answer on physics.stackexchange.com


Can dedicated circuits share a neutral?

A dedicated vs separate circuit is the argument-- As I seeit a dedicated circuit should not share a neutral and a separate circuit may share it.
Takedown request   |   View complete answer on forums.mikeholt.com


Can you put 2 neutral wires together in panel?

Bottom Line. Many homes have neutral bars that have too many neutral wires in one hole or slot. Generally this does not create a problem for the homeowner, however, it is an easy fix and most home inspectors recommend correcting the issue.
Takedown request   |   View complete answer on buyersask.com


Will a GFCI work on a multi wire branch circuit?

GFCI receptacles can be used on multiwire circuits, but they must be wired such that the neutral on the load side of the GFCI is not shared by two ungrounded conductors.
Takedown request   |   View complete answer on ecmweb.com


Can multiple switches use the same neutral wire?

If both switches are powered by the same breaker you can wire both to the same neutral.
Takedown request   |   View complete answer on diy.stackexchange.com


Are multi wire branch circuits legal?

The National Electrical Code permits multiwire branch circuits, but adds requirements to make them safer. Section 210.4(B) states that in the panelboard where the branch circuit originates, all ungrounded conductors must be provided with a means to disconnect them simultaneously.
Takedown request   |   View complete answer on jadelearning.com