Can different circuits share a ground?
So if your area has adopted NEC 2014, you can connect a grounding conductor to the grounding conductor from another branch circuit, as long as both circuits originate from the same panel.Can grounds from different circuits be tied together?
I usually tie them together but this time I thought it was cleaner to separate them. both circuits are properly grounded at the sub panel. The inspector said that for the past 30 years the code has required that all equipment grounds be tied together regardless of what circuit they originate from.Can two circuits share a neutral and ground?
What is a multiwire branch circuit? A multiwire branch circuit is a branch circuit with a shared neutral. This means there are two or more ungrounded (hot) phase or system conductors with a voltage between them and a shared neutral.Can dedicated circuits share a ground?
Yes. All grounds are connected to each other.Do you need a ground for every circuit?
Without grounding, power surges or equipment damage could render electrical circuits dangerous or destructive. They could damage attached electrical appliances, shock nearby people, or even start fires. Grounding is an important safety feature for any structure's electrical system.Shared or Borrowed Neutrals on Mains Electricity Circuits
Can 2 power supplies share a common ground?
If the two power supplies share a common ground, or can be made to, then it is no problem. However, the return wire must be sized for the sum of the 8 V and 12 V currents.Can two wires share the same ground?
The reason that wiring devices have grounding connections that accept only one wire is that otherwise, if two ground wires were connected to the device, then if someone later removed that wiring device and then re-applied power without wire-nutting the grounding conductors, there would be a break in the ground path for ...Can 2 GFCI share the same ground?
Using two individual breakers does not work because of the way that GFCI breakers are designed. They ensure that current flowing into the load on the hot wire is equal to the current flowing out of the load in the neutral wire.Can a dedicated branch circuit share a neutral?
A dedicated vs separate circuit is the argument-- As I seeit a dedicated circuit should not share a neutral and a separate circuit may share it.Can I borrow a neutral from another circuit?
No, you can't steal a neutral wire from another circuit. Each neutral wire is the return for the corresponding hot. If you "steal" a neutral from another circuit you run the risk of overloading that neutral wire (overheat, fire risk). Another issue might arise if the circuit later becomes a GFCI.Can multiple switches use the same neutral wire?
If both switches are powered by the same breaker you can wire both to the same neutral.Can two different circuits share a box?
The answer is yes you can have 2 separate circuits in the same box (they can have a splice also but not needed in your case). The only concern would be the total box fill. Based on the NEC the wire fill would be calculated at 2.0 for each conductor for 14 gauge wire and 2.25 for 12 gauge wire.How many branch circuits can share a neutral?
As you also mention, neutral conductors are not allowed for more than one branch circuit or one multiwire branch circuit or one set of ungrounded feeder conductors as stated in 200.4(A), unless specifically permitted elsewhere in this Code.Are multi wire branch circuits legal?
The National Electrical Code permits multiwire branch circuits, but adds requirements to make them safer. Section 210.4(B) states that in the panelboard where the branch circuit originates, all ungrounded conductors must be provided with a means to disconnect them simultaneously.Can receptacles share neutrals?
Yes. GFCI receptacles work fine supplied by a multi-wire circuit. GFCI circuit breakers have a separate terminal for the neutral wire which must be run with the hot wire.Is it OK to have more than one GFCI on a circuit?
The Standard Number Of GFCI's On One CircuitYou may use two or more GFCI rated outlets on one circuit if you like. However, if one trips or goes bad, all the outlets/GFCIs down the line will be affected. That's why you should test your GFCI's monthly to ensure proper operation.
Can you put a GFCI on every outlet?
You can replace almost any electrical outlet with a GFCI outlet. Correctly wired GFCIs will also protect other outlets on the same circuit. While it's common to find GFCI outlets in bathrooms and kitchens, there are GFCI outlet requirements.Can you put 2 ground wires together in panel?
Each neutral (white, grounded conductor) wire should be secured separately under its own lug/set-screw terminal in an electric panel, per National electrical Code (NEC 408.41). Also, a neutral and equipment ground (bare or green) wire cannot share a terminal.Can ground and neutral be on the same bar?
The answer is never. Grounds and neutrals should only be connected at the last point of disconnect. This would be at main panels only.Can you put two ground wires together in a breaker box?
Many panels allow doubling the grounds. It is usually noted on the panel data sheet. Anatol is correct. Usually doubling, and even tripling, of ground wires is not an issue.Can 12V and 24v share the same ground?
Yes, but only when you have a 24v alt hooked to two batterys and a second 12v alt hooked to one(of those two) battery.Can you connect two grounds together?
Whenever there is a potential difference between two ends of a ground/common path, or between two ground/common points which are connected together, the resultant current flow and voltage is what is called a ground loop.Can 12V and 5V share a ground?
Unless there is an (optical) isolator somewhere in the relay circuit, the 5V and 12V parts should share the same ground. But you should make sure the relay circuit can handle the +12V input signal.
← Previous question
Which food is not good for back pain?
Which food is not good for back pain?
Next question →
What is the best selling muscle car of all time?
What is the best selling muscle car of all time?